Heating and Cooling Dual Use Chiller
According to the hot and cold cycle test standards and requirements, hot and cold cycle temperature control machine contains high temperature medium tank and heating system, temperature control room temperature 10C-90C, low temperature tank and cooling system, temperature range, room temperature to minus 40C, temperature control precision is 2C, heating and cooling time does not exceed 90 minutes, the media slot designed to equal capacity 350L (actual effective volume of 240L), pressure 0.6MPA, reserved outside the interface into the media valve, the whole part of the high and low temperature insulation or Water basin design, to prevent condensate leakage.
|
High Temp Control Range |
℃ |
40~ 90 |
||
|
Low Temp Control Range |
℃ |
-40~ 40 |
||
|
System Display Accuracy |
℃ |
0.1 |
||
|
Temp Control Accuracy |
℃ |
±2 |
||
|
Rated Power |
Kw |
56 |
||
|
Nominal Heating Capacity |
Kw |
21.6 |
||
|
Nominal Cooling Capacity |
Kw |
13.9 (-20~ -40) |
||
|
Kw |
18.6 (40~ -20) |
|||
|
High Temp Medium Tank |
Volume |
L |
350 |
|
|
Thickness |
mm |
3 |
||
|
Pressure |
Mpa |
0.6 |
||
|
Material |
SS304 |
|||
|
Insulated Way |
B1 Insulated Cotton, 10mm |
|||
|
Heating Capacity |
Kw |
12+12 |
||
|
Pump Power |
Kw |
0.37 |
||
|
Low Temp Medium Tank |
Volume |
L |
350 |
|
|
Thickness |
mm |
3 |
||
|
Pressure |
Mpa |
0.6 |
||
|
Material |
SS304 |
|||
|
Insulated Way |
B1 Insulated Cotton, 10mm |
|||
|
Cooling Capacity |
Kw |
11+18.75 |
||
|
Pump Power |
Kw |
1.5 |
||
|
Cooling Tower Water |
Flow |
M3/h |
30 |
|
|
Temp |
℃ |
32 |
||
|
Pipe Size |
mm |
DN80 |
||
|
Water Pressure |
MPA |
0.3 |
||
|
Refrigerant |
Control Way |
Expansion Valve |
||
|
Model |
R404A |
|||
|
Charge |
KG |
9+15 |
||
|
Other Specs |
Ambient temp |
℃ |
≤40 |
|
|
Max Current |
A |
23 |
||
|
Unit Weight |
KG |
620 |
||
|
Dimension |
mm |
4500*1700*1830 |
||
Hot Tags: heating and cooling dual use chiller China, manufacturers, plant, price, for sale