Common problems and solutions of industrial chillers summarized by Anyda
1. Water leakage (first determine the location of the water leakage)
1. The pump leaks (causes: the shaft seal at the water pump is not well connected or the shaft seal has been damaged)
Solution: do not change the shaft seal, directly change the pump
2, the water tank leaks (cause: trachoma appears in the welding position of the water tank or it is used for a long time)
Solution: Pull back to the manufacturer to re-weld the leaking position
3, ball valve, diverter (cause: ball valve, diverter leaks)
Solution: Replace the ball valve and diverter
4. The connection position of the horn of the tube (Cause: water leaks at the connection position of the same horn)
Solution: disassemble and re-fire the bell mouth, reinstall
5. The position of the floating ball is leaking (cause: the floating ball has fallen or the position of the floating ball is incorrectly adjusted)
Solution: reinstall the float ball and adjust the position of the float ball
2. No cooling (causes: system leakage of refrigerant, broken compressor, broken computer board, overload)
1. System leakage of refrigerant (check method: first look at the low pressure gauge, there is no pressure, no pressure, indicating the type of refrigerant leakage)
Solution: Check for leaks and make up for leaks, check not one of the copper pipe connections, and see where the snow is leaking
2. The compressor is broken (compressor failure will also be displayed) (check method: use a clamp meter to clamp the three wires of the compressor to get the working current, if the three are different, the preliminary judgment is that the compressor is broken; the current of the 5HP compressor is 9A -10A current is normal, otherwise it is abnormal)
Solution: Replace the compressor
3, the computer board is broken (the temperature displayed on the computer board is abnormal, or does not match the actual temperature)
Solution: Replace the computer board
4. Overload (the temperature will not reach the predetermined effect during the use of the chiller, or the temperature will rise instead of falling)
Solution: It means that the power of the optional chiller is not large enough, and it may be necessary to replace a larger chiller to set the required temperature
3. the chiller reports a low pressure failure
1. System leakage of refrigerant (check the low pressure gauge first, whether there is pressure, if there is no pressure or the pressure is low, it means that the type of refrigerant is leaking)
Solution: Check the leakage and repair the leakage, check each copper pipe connection, and see where the snow is leaking
2, the pressure controller is broken
Solution: Check whether the pressure controller can be reset, if it cannot be reset, replace the pressure controller
3, the computer board is broken (there is no other problem, it may be a low voltage failure caused by a computer program error)
Solution: Replace the computer board and re-adjust the parameters
4. The filter is blocked (one side of the filter and capillary tube is lower, and the temperature on the other side will not change, it means the filter is blocked)
Solution: Replace the filter
4.high-pressure alarm (turn on the high-pressure meter, if it keeps rising, a high-pressure alarm will appear)
Generally, it is not the manufacturer’s problem, and the customer’s problem can be solved from the following
1. Is the water in the water tower turned on? Is the cooling water path unobstructed?
2. Will the water quality of the water tower be very good? If you have used it for more than half a year without checking the blisters, you need to clean the water monitor
4. If it is air-cooled, clean the condenser if it is worn out
5. If none of the above points can solve the problem, it may be a problem with the pressure controller and the computer board. You need to replace the pressure controller or the computer board.